The LPT‐A Vent Line Ammonia Transmitter (LPT‐A‐VLT‐NH3‐S) is designed for continuous monitoring of ammonia levels in the vent lines of refrigeration systems caused by equipment failure or system over pressurization. Slow leaks of refrigerant can be costly over time and a dangerous situation could present itself if a high pressure release were to occur. Typically, normal vapour flow is handled by the ammonia compressor, but a vapour flow in excess of the compressor’s capacity will enter the vent stack and can cause a large amount of the gas to travel up the vent line and discharge. In addition, higher than normal concentrations of ammonia can be caused by faulty valves, damaged or worn equipment, contaminants and/or equipment failure or system overpressure. Without safety precautions in place, hazardous levels of ammonia from equipment failure or over pressurization could cause an explosion and seriously jeopardize the health of workers and people in the surrounding area.
เซนเซอร์สำหรับตรวจวัดแอมโมเนียที่ออกแบบมาเฉพาะสำหรับติดตั้งที่ช่องระบายของระบบทำความเย็น เพื่อวัดระดับแอมโมเนียหากเกิดข้อผิดพลาดขึ้นในระบบ หรือเมื่อมีแรงดันในระบบมากเกินไป ซึ่งเหตุการณ์เหล่านี้ นำมาซึ่งการรั่วออกของแอมโมเนียอย่างช้าๆ และเมื่อมีการระบายออกของแอมโมเนียสะสมในปริมาณมาก ก็จะเกิดอันตรายกับผู้คนในบริเวณโดยรอบ บางครั้งอาจส่งผลถึงการสูญเสียชีวิต |
The VLT provides continuous, real‐time monitoring of the levels of ammonia in the relief vent line. It can be configured to alarm at a pre‐determined set point (1.0% / 10,000 ppm is recommended) and send an analog signal to activate a remote strobe or horn, or communicate with a controller or PLC to activate or shut down equipment as required.
The catalytic NH3 sensor has a range of 0 to 3% volume (0 – 30,000 ppm) and is potted into a 2” pipe fitting protruding from the back of the enclosure which connects to a coupler that is used to secure the device to a mounting pipe. The LPT‐A‐VLT‐NH3‐S may be mounted on the vent relief stack above the pressure relief valve using the 3/4” cast steel coupler. Or it can be mounted outside on the relief header, 3 to 5 feet above the roofline. Unless exposed to very high concentrations of ammonia for a prolonged period of time, the sensor should last 3+ years.
The VLT is virtually maintenance free, but removal from the pipe extension will be required to access the sensor during calibration. Bump tests should be done monthly and a full calibration conducted yearly (unless a significant exposure incident occurs, after which additional bump tests and/or calibrations are required to ensure the device is working properly and the sensor has not been poisoned).