AMMONIA GAS DETECTION SYSTEMS

ระบบตรวจจับก๊าซ AMMONIA ตำแหน่งติดตั้งเซนเซอร์ก๊าซแอมโมเนีย และ การบำรุงรักษาเซนเซอร์แอมโมเนีย

AMMONIA GAS DETECTION SYSTEMS

Ice rinks
Chiller rooms
Cold storage
Manufacturing plants
– Fertilizer
– Pharmaceuticals and cosmetics
– Textiles
– Ammonia
Supermarkets

Convenience Stores
Ice cream plants
Ice making plants
Meat packing and processing plants
Universities
Food processing plants
Wineries and breweries
Food distribution centers
Livestock facilities
Chemical storage rooms
Hospitals

CXT Explosion Proof Transmitter Sensor Type Electrochemical Sensor Range 0 – 500 ppm
Default Factory Alarm Setpoints Low: 25 ppm Mid: 35 ppm High: 250 ppm

AT WHAT HEIGHT SHOULD THE GAS DETECTOR BE MOUNTED?
Ammonia is lighter than air and collects at the ceiling (or the highest point of the room). Therefore the gas detector/sensor should be mounted on or at the ceiling. If you were to mount the detector at breathing height (1.2 – 1.8 m / 4 – 6 ft from the floor), the concentration of ammonia would start at the ceiling and move down towards the breathing height as more and more leaked and collected. By the time the ammonia level was at breathing height, the room would be so full of ammonia, not only would it be a breathing hazard, but also an explosion/fire hazard, not to mention the high cost of losing all that ammonia. The goal is to be alerted of an ammonia leak as soon as possible so safety measures can be taken to stop and repair it.


NOTE: In the presence of moisture (such as high relative humidity), ammonia gas forms vapour that is heavier than air and may spread along areas with poor air flow where people may be exposed.

WHAT IS A BUMP TEST AND WHY SHOULD THEY BE DONE?
A bump test is a brief exposure of the sensor to gas and verifies if the sensor is responding and the alarm is functioning.
HOW OFTEN SHOULD AN AMMONIA GAS DETECTOR BE BUMP TESTED?
At minimum, the ammonia gas detector should be bump tested once a month as part of the monthly maintenance plan for
the device. There is no limit on the number of bump tests; they may be done more often depending on application and the
comfortability/confidence level one has in the device and how it responds. If a bump test fails, a full calibration should be done.
Bump test dates and results should be written down in a log book.
WHAT IS CALIBRATION AND WHY SHOULD IT BE DONE?
Calibration is the exposing of the sensor to a certified concentration of gas for a particular length of time and verifies that the gas detector is providing an accurate reading.
HOW OFTEN SHOULD AN AMMONIA GAS DETECTOR BE CALIBRATED?
At minimum, the gas detector should be calibrated every 6 month. More frequent calibrations may be required depending on
application, regulatory laws, sensor response and exposure levels to the gas. If a bump test fails, a full calibration should be done. Calibration dates and results should be written down in a log book.
WHAT IS THE LIFESPAN OF AN AMMONIA SENSOR?
The lifespan of an ammonia sensor is measured in ppm hours. The more gas the sensor sees (constant exposure), the shorter the life span of the sensor. A high concentration all at once will poison it and render it useless.
WHERE DO I FIND MORE INFORMATION ABOUT AMMONIA SAFETY STANDARDS AND REGULATIONS?
Check your local/provincial/state’s:
• Safety Standards Act for gas safety regulations
• WorkSafe regulations


ระบบตรวจจับก๊าซ AMMONIA ตำแหน่งติดตั้งเซนเซอร์ก๊าซแอมโมเนีย และ การบำรุงรักษาเซนเซอร์แอมโมเนีย


CXT Explosion Proof Transmitter เครื่องตรวจจับก๊าซแอมโมเนีย (Ammonia)NH3 ประเภทเซนเซอร์ เซนเซอร์ไฟฟ้าเคมี ช่วง 0-500 ppm
การตั้งค่ามาตรฐานคือ: Low: 25 ppm Mid: 35 ppm High: 250 ppm

เครื่องตรวจจับก๊าซแอมโมเนีย (Ammonia)NH3มีน้ำหนักเบากว่าอากาศ (หรือจุดสูงสุดของห้อง) ดังนั้นเครื่องตรวจจับก๊าซ / เซนเซอร์ควร
ติดตั้งบนผนังหรือที่เพดาน หากต้องการติดตั้งเครื่องตรวจจับก๊าซแอมโมเนีย (Ammonia)NH3 ที่ความสูงของการหายใจ (1.2 – 1.8 m / 4 – 6 ฟุตจากพื้น),
ความเข้มข้นของเครื่องตรวจจับก๊าซแอมโมเนีย (Ammonia)NH3จะเริ่มต้นที่เพดานและเลื่อนลงไปที่ระดับความสูงขณะที่มีการรั่วไหลมากขึ้น
เมื่อถึงเวลาที่ระดับเครื่องตรวจจับก๊าซแอมโมเนีย (Ammonia)NH3อยู่ในระดับความสูงห้องก็เต็มไปด้วยแอมโมเนีย ไม่เพียงแต่จะเป็น
อันตรายต่อการหายใจ แต่ยังเป็นอันตรายจากการระเบิด เป้าหมายคือการแจ้งให้ทราบถึงการรั่วซึมของแอมโมเนียโดยเร็วที่สุดเท่าที่จะเป็นไปได้
เพื่อให้สามารถใช้มาตรการด้านความปลอดภัยต่อโรงงานหรือสถานที่ ที่อาจจะทำให้เกิดก๊าซแอมโมเนียได้่

หมายเหตุ: ในที่ที่มีความชื้น (เช่นความชื้นสัมพัทธ์สูง) เครื่องตรวจจับก๊าซแอมโมเนีย (Ammonia)NH3จะเกิดไอระเหยที่หนักกว่าอากาศและอาจ กระจายไปตามพื้นที่ที่มีการไหลของอากาศ

อะไรคือการทดสอบ BUMP ?
การทดสอบการชนคือการสัมผัสเซ็นเซอร์กับแก๊ส เครื่องตรวจจับก๊าซแอมโมเนีย (Ammonia)NH3 และตรวจสอบว่าเซ็นเซอร์ตอบสนองหรือไม่ สัญญาณเตือนทำงานอยู่หรือไม่
วิธีการที่ควรเครื่องตรวจจับก๊าซแอมโมเนียถูกทดสอบ BUMP?

LIFESPAN OF OF AMMONIA SENSOR คืออะไร?
อายุการใช้งานของเซ็นเซอร์เครื่องตรวจจับก๊าซแอมโมเนีย (Ammonia)NH3วัดได้ในหน่วยพีพีเอ็ม

Girl in a jacket